Standard DC Power Distribution Center
![]()
LDC2-Series
Hot "swappable" circuit breakers that can be installed, changed, or replaced in the field or factory Circuit breakers are front panel accessible Incorporates Carling C-Series hy-mag breakers, providing superior level of performance Maximum of six UL489 listed breakers per feed, 12 per panel Versatile design combines circuit breaker and GMT fuse protection in one panel One Rack Unit (1RU) size Panel plugs provided for non-populated circuit breaker slots Short handle circuit breakers to prevent accidental operation Panel easily configurable and upgradeable in the field, providing flexibility when designing added features or options Conserves valuable cabinet space Breaker installation/removal tool available upon reques
| Series PDF eLibrary | |
| Standards | UL1801, CUL Approved (pending) |
| Dimension | Rack mounts to EIA standard EIA-310-D 23" rack for a 1RU panel, 1.75" H |
| Enclosure | 16 gauge yellow zinc chromate cold rolled steel |
| Feeds | Dual feeds, rated up to 150 amps per feed Maximum circuit breakers per feed: 6 Maximum breaker rating: 50 amps GMT fuses feeds rated to 40A Maximum GMT fuses per feed: 4 Maximum fuse rating: 10A |
| Load Connections | Requires 1 awg wire/ring or fork terminal for 50A/75 degrees C Rating, top or bottom wire entry |
| Operating Voltage | -36V to -60V DC (-48VDC nominal) |
| Alarm Feature | Power alarm: If either A or B Feed fail or both fail Breaker Alarm: If any populated breaker is OFF or "tripped". Alarm is not affected by unused breaker positions Fuse alarm: Alarm indication if any GMT fuse opens LED indicators on the front panel |
| LED Indicators | Green lamps on A and B feeds Red lamp for alarm indication |
| Chassis Ground | Via studs on back panel, use two hole x 5/8" center lugs.Via rack mounting via brackets to yellow zinc chromate steel panel enclosure on the PDC |